100

Figure 5-3: KC1000 Air/Fuel Valve In Purge Position

4. Next, the blower proof switch (Figure 5-4) closes and the display will show Purging and

indicate the elapsed time of the purge cycle in seconds. The normal (default) time for
the purge cycle is 7 seconds.

154

155

AIR/FUEL VALVE

BLOWER PROOF

SWITCH

TO FRAME

HARNESS

Figure 5-4; Blower Proof Switch

5. Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the

following events occur:

(a)

The Air/Fuel Valve rotates to the low-fire ignition position and closes the ignition
switch. The dial on the Air/Fuel Valve (Figure 5-5) will read between 25 and 35 to
indicate that the valve is in the low-fire position.

(b)

The igniter relay is activated and provides ignition spark.

(c)

The gas Safety Shut Off Valve (SSOV) is energized (opened) allowing gas to
flow into the Air/Fuel Valve. Up to 7 seconds will be allowed for ignition to be
detected. The igniter relay will be turned off one second after flame is detected.