2.9 COMBUSTION CAL MENU
The Combustion Cal (Calibration) Menu items are used to vary the speed of the unit’s blower
motor based on air temperature and air density at prescribed Air/Fuel Valve positions. These
valve positions (% open) may vary depending on the Unit Type and Fuel selected in the
Configuration Menu (Table 2-3). The blower motor speed is varied by providing a DC drive
voltage to the motor which adjusts the rotational speed of the blower to maximize combustion
efficiency.
C-More controllers with software Version 3.07.xx, used on all Benchmark (BMK) sizes and all
KC1000 units, check calibration at 6 prescribed valve positions. Table 2-6 shows a sample
listing, which applies to BMK 750 MBH and BMK 1000 MBH using Natural Gas. Refer to Table
3-2A for default values associated with each unit type and size.
Table 2-6: Sample Combustion Cal Menu (Version 3.07.xx)
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
CAL Voltage 18%
.25v
8.20v
1.80v
CAL Voltage 30%
.25v
8.20v
3.20v
CAL Voltage 45%
.25v
8.20v
3.70v
CAL Voltage 60%
.25v
8.20v
3.80v
CAL Voltage 80%
.25v
8.20v
4.60v
CAL Voltage 100%
.25v
8.20v
6.00v
SET Valve Position
0%
100%
0%
Blower Output
Monitor Blower Output
Voltage
.00
C-More controllers with software version 3.08.xx, used on Innovation (INN) Water Heaters,
check calibration at 8 prescribed valve positions. Table 2-7 shows a sample listing which applies
to INN 1060 units running on Natural Gas. Refer to Table 3-2B for default values associated
with each INN unit size and fuel used.