Table 2-7: Sample Combustion Cal Menu (Version 3.08.xx)
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
CAL Voltage 16%
.25v
8.20v
1.90v
CAL Voltage 20%
.25v
8.20v
2.30v
CAL Voltage 30%
.25v
8.20v
2.80v
CAL Voltage 40%
.25v
8.20v
3.00v
CAL Voltage 50%
.25v
8.20v
3.60v
CAL Voltage 60%
.25v
8.20v
3.90
CAL Voltage 80%
.25v
8.20v
4.80
CAL Voltage 100%
.25v
8.20v
6.00v
SET Valve Position
0%
100%
0%
Blower Output
Monitor Blower Output
Voltage
.00
2.10 CALIBRATION MENU
The Calibration Menu is used by Factory Trained Service personnel to adjust or reset the
parameters listed in Table 2-8.
Table 2-8: Calibration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Stepper Fbk
(Not adjustable via RS232
serial communication)
Cal 0%
Cal 100%
Verify 50%
Cal 0%
PWM In Adj
-5.0%
5.0%
0.0%
Supply Gas Pressure In Adj
-5.0%
5.0%
0.0%
Gas Plate dp In Adj
-5.0%
5.0%
0.0%
mA Out Adj
-1.0 mA
1.0 mA
0.0 mA
A/F Sensitivity
1%
5%
2%
Power Reset
Automatic orManual
Automatic
Water Temp Reset
Automatic or Manual
Automatic
Gas Press Reset
Automatic or Manual
Manual
Min Off Time
0 Min
15 Min
1 Min (Boiler)
0 Min (Water
Heater)
Heatr Tuning Dsp
(If Unit Type = Water Heater)
Enabled or Disabled
Disabled