C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual
Page 52

C-More Controller for Benchmark, Innovation & KC
USER MANUAL
Page 52 of 162
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
04/22/14
GF-112
Phone: 800-526-0288
OMM-0032_0E
Table 3-2A: Combustion Cal Menu Default Settings (Version 3.07.xx)
CALIBRATION POINTS
Valve Position % Open
Default Voltage Settings
UNIT TYPE & SIZE
FUEL
18%
30%
45%
60%
80%
100%,
BMK 750 1000 & 1.5
Nat. Gas
1.80v
3.20v
3.70v
3.80v
4.60v
6.00v
16%
30%
45%
60%
70%
75%,
Propane
2.25v
3.95
2.70v
2.25v
2.60v
6.00v
16%
30%
45%
60%
80%
100%,
BMK 750 ,1000, 1.5
Dual Fuel
Nat. Gas
1.80v
3.20v
3.70v
3.80v
4.60v
6.00v
16%
30%
45%
60%
70%
75%,
Propane
2.25v,
3.95v
2.70v
2.25v
2.60v
6.00v
14%
30%
40%
50%
70%
100%,
BMK STD 2.0
Nat. Gas
1.00v
2.30v
2.95v
3.60v
5.30v
9.10v
14%
30%
40%
50%
70%
100%,
Propane
1.10v
1.95v
3.00v
3.00v
4.45v
8.20v
14%
30%
40%
50%
70%
100%,
BMK STD 2.0
Dual Fuel
Nat. Gas
1.00v
2.30v
2.95v
3.60v
5.30v
9.10v
14%
30%
40%
50%
70%
100%,
Propane
1.10v
1.95v
3.00v
3.00v
4.45v
8.20v
18%
30%
45%
60%
80%
100%,
BMK LN CP 2.0
Nat. Gas
1.00v
2.30v
2.95v
3.60v
5.30v
9.10v
20%
30%
45%
60%
80%
100%,
Propane
1.10v
1.95v
3.00v
3.00v
4.45v
8.20v
20%
30%
45%
60%
80%
100%,
BMK LN CP 2.0
Dual Fuel
Nat. Gas
1.00v
2.30v
2.95v
3.60v
5.30v
9.10v
21%
30%
45%
60%
80%
91%,
Propane
1.10v
1.95v
3.00v
3.00v
4.45v
8.20v
16%
30%
40%
50%
70%
100%,
BMK 1500
Nat. Gas
1.00v
2.30v
2.50v
2.90v
3.80v
7.90v
18%
30%
40%
50%
70%
100%,
Propane
1.20v
2.30v
2.80v
3.00v
3.50v
7.70v
16%
30%
40%
50%
70%
100%,
BMK 1500
Dual Fuel
Nat. Gas
1.50v
2.60v
3.20v
3.30v
4.10v
8.30
18%
30%
40%
50%
70%
100%,
Propane
1.20v
2.30v
2.80v
3.00v
3.50v
7.70v