C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 108 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

The displayed item groups are displayed in UPPER CASE letters, and are bounded by an
asterisk * in order to readily identify them within the item list.

The items contained in group 1 (BST Monitor Items) are ALWAYS displayed within the menu, as
these items are critical for proper system operation. Therefore, the BST Monitor Items Header
itself is NOT displayed.

The Items contained in groups 2-5 are NOT displayed unless that particular item group has
been enabled from the C-More keypad.

Menu Item Chart

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

BST Mode

Off

BST Slave

BST Master

Off

BST Setpoint

BST Setpt Lo Limit

BST Setpt Hi Limit

130°F

Header Temp

NA

Header Temp

(°F)

BST Fire Rate

0

100%

Fire rate %

BST Ave Fire Rate

0

100%

Avg Fire Rate %

BST Outdoor Temp

NA

Outdoor Temp

(°F)

Units Available

0

8

Units Present

Units Ignited

0

8

Units firing

BST Valve State

0 (CLOSED)

1 (OPEN)

0

1 Comm Errors 8

0

9

0

1 BST Units 8

0 (see table)

0 (see table)

0

*BST SETUP MENU*

Disabled

Enabled

Disabled

BST Setpoint Mode

Constant

Setpoint

Remote Setpoint

Outdoor Reset

Constant Setpt

Head Temp Source

Network

FFWD Temp

FFWD Temp

Header Temp Addr

0

255

240

Header Temp Point

0

255

14

BST Outdoor Sens

Disabled

Enabled

Disabled

Outdr Tmp Source

Outdoor Temp

Network

Outdoor Temp

Outdoor Tmp Addr

0

255

240

Outdoor Tmp Pnt

0

255

215

BST Remote Signal

4-20 mA/1-5 Vdc;

0-20 mA/0-5

Vdc;

Network

Network

BST Auto Mstr

No

Yes

NOTE! A Modbus temperature
transmitter must be installed in
conjunction with this feature.

No

BST Auto Timer

10 sec

120 sec

30 sec

Remote Intlk Use

Boiler Shutdown

System Shutdown

System

Shutdown

One Boiler Mode

Off

On-Outlet

Temp

On-Avg Temp

Off

1 Blr Threshold

10

35

25