C-More Controller for Benchmark, Innovation & KC
USER MANUAL
04/22/14
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913
Page 31 of 162
OMM-0032_0E
Phone: 800-526-0288
GF-112
Table 2-9: Diagnostics Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Exhaust Temp Sens
Enable, Disable
Disable
In Wtr Temp Sens
Enable, Disable
Disable
In Gas Press Sen
Enable, Disable
Disable
Gas Plate dp Sen
Enable, Disable
Disable
In Water Flw Sen
Enable, Disable
Disable
Display Test
Off, LEDs, 7-Seg Bar-graph
Off
Keypad Test
Off, Manual, Menu Up, Down, Change, Enter, Clear
(BACK Key exits test mode)
Off
Relay Test
(Allows user to force
outputs ON or OFF)
Off, Igniter ON/Igniter OFF, Blower ON/Blower OFF
Pump ON/Pump OFF, Aux ON/Aux OFF
Fault ON/Fault OFF
Off
Switch Test
(Allows user to view the
status of all switch
inputs)
Off, Exhaust sw ON/Exhaust sw OFF
SSOV sw ON/SSOV sw OFF
Blower Proof ON/Blower Proof OFF
Ignition sw ON/Ignition sw OFF
Over Temp sw ON/Over Temp sw OFF
Low Gas Pres ON/Low Gas Pres OFF
Hi Gas Pres ON/Hi Gas Pres OFF
Water Lev sw ON/Water Lev sw OFF
Rem Int sw ON/Rem Int sw OFF
Front Pnl sw ON/Front Pnl sw OFF
Delayed Int ON/Delayed Int OFF
Purge sw ON/Purge sw OFF
Off
Stepper Test
(Allows user to adjust
the stepper motor
position using the
▲
and
▼ keys)
0%
100%
0%
Sensor Log Int
(Allows user to set the
time interval for logging
Sensor inputs in
Database)
Off
1 Min, 5 Min, 15 Min, 30 Min
1 Hr, 6 Hrs, 12 Hrs, or 24 Hrs
30 Min.