Table 3-1: Menu Item Descriptions - Continued
MENU LEVEL & OPTION
DESCRIPTION
Tuning Menu (Continued)
Outlet Feedback
Used to Enable or Disable feedback. Disable this function for Feed-
Forward control only.
Feedback Gain
(If Unit Type = Water
Heater)
Adjustable from 0.01 to 1.00 (Default is 0.05).
Breakpoint at 100%
Thru Breakpoint at 0%
(If Unit Type = Water
Heater)
Allows breakpoint temperature settings to be entered for 100% to
0% in 10% increments. The Bkpt Dsp options in the Calibration
Menu must be enabled to view breakpoint temperatures. See Table
2-4 for breakpoint default values.
WARMUP: The feature embodied in the following three menu items eliminates Temperature
Overshoots during the “Warmup” period of a cold ignition cycle on all boilers by temporarily
modifying the PID Gain parameter during warmup and for a period defined in the Tuning Menu.
Warmup Prop Band
Range = 1-120
Default = 95
Warmup Int Gain
Range = 1-200
Default = 50
Warmup PID Timer
Range = 1-240
Default = 20
Reset Defaults?
Resets Tuning Menu options to Factory Defaults
Water Heater Management (WHM) Menu – (Software Version 3.08.xx Only)
Password Level 1 Options:
WHM Mode
This option is used to enable/disable the WHM Mode and set the
unit to function as a WHM Slave, or WHM Master. (Default = Off)
WHM Setpoint
This is the temperature (°F) that each unit in the WHM system is
trying to control to. (Default = 130°F)
Next On VP
This is the Next On A/F Valve position (%) for the system. When all
enabled water heaters have a fire rate greater than this value, it is
time to enable another water heater, if one is available. This value
should always be greater than the Next Off A/F Valve, and there
should be a reasonable spread between the 2 values.
(Default = 65%)
Next Off VP
This is the Next Off A/F Valve position (%) for the system. When all
enabled water heaters have a A/F Valve position greater than this
value, it is time to enable another water heater, if one is available.
This value should always be greater than the Next Off A/F Valve
position, and there should be a reasonable spread between the 2
values. (Default = 35%)
Lead/Lag Hours
This feature is basically designed spread the total number of run
hours accumulated on all units in the system so that each of the
units have approximately the same number of run hours. The
default value for this option is 72 hours,
WHM Upload Timer
Communication data logging period in seconds between 0 to 9999.
A value between 60 and 120 seconds is recommended.
Note: If OnAER is enabled for WHM the Min Upload Timer in the
Setup Men should be set between 300-600 seconds.