C-More Controller for Benchmark, Innovation & KC

USER MANUAL

Page 112 of 162

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

04/22/14

GF-112

Phone: 800-526-0288

OMM-0032_0E

This item displays the number of Comm errors on each Comm port (slave Unit). If no valid
address is entered for a slave unit, the display will read “-” for that address. The Max number of
error count is 9.


1 BST Unit 8
This item displays eight characters representing the status of each of the possible eight units on
the network.

Symbol

Explanation

1

ON

0

Off

-

Offline

*

Not Available

S

Setpoint Limiting is active

A

Lead unit

B

Lag Unit

a

Lead Off

b

Lag Off



Example of

1 BST Unit 8 display:



1 BST Units 8
A b 0 1 S * - -

Unit #1 is the Lead
Unit and is Ignited

Unit #2 is the Lag
Unit and is Off

Unit #3 is Off

Unit #4 is Ignited

Unit #5 is ignited
and is in Setpoint
Limiting Mode

Unit #6 is either
disabled or Faulted

Units #7 & 8 are
not installed or
connected to the
MODbus network