beautypg.com

C-more controller for benchmark, innovation & kc – AERCO C-More Controls Manual June 2010 User Manual

Page 43

background image

C-More Controller for Benchmark, Innovation & KC

USER MANUAL

04/22/14

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, New York 10913

Page 43 of 162

OMM-0032_0E

Phone: 800-526-0288

GF-112

Table 3-1: Menu Item Descriptions - Continued

MENU LEVEL & OPTION

DESCRIPTION

Diagnostic Menu

Exhaust Tmp Sens

Allows the Enabling or Disabling of the alternating warning and fault
messages on the VFD display for EXHAUST TEMPERATURE
Default is Disabled. (See Table 3-1A)

In Wtr Tmp Sens

Allows the Enabling or Disabling of the alternating warning and fault
message on the VFD Display for INLET WATER TEMPERATURE.
Default is Disabled. (See Table 3-1A)

In Gas Press Sen

Allows the Enabling or Disabling of the alternating warning and fault
message on the VFD Display for INLET GAS PRESSURE. Default
is Disabled. (See Table 3-1A)

Gas Plate dp Sen

Allows the Enabling or Disabling of the alternating warning and fault
message on the VFD Display for GAS PLATE DIFFERENTIAL.
Default is Disabled. (See Table 3-1A)

In Water Flw Sen

Allows the Enabling or Disabling of the alternating warning and fault
message on the VFD Display for INLET WATER FLOW. Default is
Disabled. (See Table 3-1A)

Display Test**

Allows testing of the front panel LED indicators, 3-character, 7-
segment LED Outlet Temperature display and 20-segment LED
Bargraph.

Keypad Test**

Allows testing of the operational status of each front panel key. The
VFD will display the name of each key as it is pressed.

Relay Test**

Allows user to force relay outputs ON or OFF. The relays tested
include: Igniter, Blower, Pump, Aux and Fault relay.

Switch Test**

Allows the ON/OFF status of all switch inputs to be viewed. These
switches include: Exhaust, SSOV, Blower Proof, Ignition, Over-
Temp, Low Gas Pres, Hi Gas Pres, Water Lev, Rem Int, Front Pnl,
Delayed Int and Purge switches.

Stepper Test**

Allows adjustment of the Air/Fuel Valve stepper motor position

using the ▲ and ▼ keys. The Bargraph display will light to indicate
the current stepper motor position.

Sensor Log Int

Allows the Sensor Log Interval to be set to: 1 Min, 5 Min, 15 Min,
30 Min, 1 Hr, 6 Hrs, 12 Hrs or 24 Hrs. Default setting is 30 Min.


**Not Adjustable via RS232 Serial Port

This manual is related to the following products: