CHAPTER 5 – MODE OF OPERATION

Page 70 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

Indoor/Outdoor Startup

1. Refer to the Indoor/Outdoor reset ratio charts in Appendix F.
2. Choose the chart corresponding to the desired Building Reference Temperature.
3. Go down the left column of the chart to the coldest design outdoor air temperature

expected in your area.

4. Once the design outdoor air temperature is chosen, go across the chart to the desired

supply header temperature for the design temperature chosen in step 3.

5. Next, go up that column to the Reset Ratio row to find the corresponding reset ratio.
6. Access the Configuration Menu and scroll through it until the display shows Bldg Ref

Temp. (Building Reference Temperature). If necessary, refer to section 3.3 for detailed

instructions on menu changing.

7. Press the CHANGE key. The display will begin to flash.
8. Use the ▲ and ▼ arrow keys to select the desired Building Reference Temperature.
9. Press ENTER to save any changes.
10. Next, scroll through the Configuration Menu until the display shows Reset Ratio.
11. Press the CHANGE key. The display will begin to flash.
12. Use the ▲ and ▼ arrow keys to select the Reset Ratio determined in step 5.
13. Press ENTER to save the change. This completes

5.3 CONSTANT SETPOINT MODE

The Constant Setpoint mode is used when a fixed header temperature is desired. Common

uses of this mode of operation include water source heat pump loops, and indirect heat

exchangers for potable hot water systems or processes.
No external sensors are required to operate in this mode. While it is necessary to set the

desired setpoint temperature, it is not necessary to change any other temperature-related

functions. The unit is factory preset with settings that work well in most applications. Prior to

changing any temperature-related parameters, other than the setpoint, it is suggested that an

AERCO representative be contacted. For descriptions of temperature-related functions and

their factory defaults, see Appendices A and E.

5.3.1 Setting the Setpoint

The setpoint temperature of the unit is adjustable from 40°F to 240°F. To set the unit for

operation in the Constant Setpoint Mode, the following menu settings must be made in the

Configuration Menu:

Menu Option

Setting

Boiler Mode

Constant Setpoint

Internal Setpt

Select desired setpoint using ▲ and ▼ arrow keys (40°F to 240°F)


Refer to section 3.3 for detailed instructions on changing menu options.