AERCO BMK 2000DF User Manual

Page 109

background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 8 – TROUBLESHOOTING GUIDE

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 109 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

TABLE 8-1: BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

HIGH GAS

PRESSURE

1.

Incorrect supply gas pressure.

2.

Defective SSOV Actuator.

3.

Defective High Gas Pressure

Switch.

1.

Check to ensure gas pressure at inlet of SSOV does not

exceed 14” W.C.

2.

If gas supply pressure downstream of SSOV Actuator cannot

be lowered to the range of 3.6” ± 0.2” W.C. for BMK1500 or
3.9” ± 0.2” W.C.

for BMK2000 using the gas pressure

adjustment screw (see section 4.3.1 or 4.3.2, step 10), the

SSOV Actuator may be defective.

3.

Remove the leads from the high gas pressure switch.

Measure continuity across the common (C) and normally

closed (NC) terminals with the unit not firing. Replace the

switch if continuity does not exist.

HIGH WATER TEMP

SWITCH OPEN

1.

Faulty Water temperature switch.

2.

Incorrect PID settings.

3.

Faulty shell temperature sensor.

4.

Unit in Manual mode.

5.

Unit setpoint is greater than Over

Temperature Switch setpoint.

6.

System flow rate changes are

occurring faster than units can

respond.

1.

Test the temperature switch to insure it trips at its actual water

temperature setting.

2.

Check PID settings against Menu Default settings in Appendix

D. If the settings have been changed, record the current

readings then reset them to the default values.

3.

Using the resistance charts in the Appendix C, Measure the

resistance of Shell sensor and BTU sensor at a known water

temperature.

4.

If unit is in Manual Mode switch to Auto Mode.

5.

Check setpoint of unit and setpoint of Temperature Switch;

Ensure that the temperature switch is set higher than the

unit’s setpoint.

6.

If the system is a variable flow system, monitor system flow

changes to ensure that the rate of flow change is not faster

than what the units can respond to.

HIGH WATER

TEMPERATURE

1.

See HIGH WATER

TEMPERATURE SWITCH OPEN.

2.

Temp HI Limit setting is too low.

1.

See HIGH WATER TEMPERATURE SWITCH OPEN.

2.

Check Temp HI Limit setting.

IGN BOARD

COMM FAULT

1.

Communication fault has occurred

between the PMC board and

Ignition/Stepper (IGST) board.

1.

Press CLEAR button and restart unit. If fault persists, contact

qualified Service Personnel.