Benchmark 1500DF - 2000DF Boilers

CHAPTER 4 – INITIAL START-UP

Page 66 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

Figure 4-5: Over-Temperature Limit Switch Locations

4.7.1 Digital Alarm Switch Checks and Adjustments

The digital alarm switch settings can be checked or adjusted using the controls and display on

the front panel of the switch illustrated and described in Figure 4-6 and Table 4-1.

F

Alarm

RST

SET

Limit Control

Figure 4-6: Digital Over-Temperature Alarm Switch Front Panel

Table 4-1: Digital Alarm Switch Controls and Display

CONTROL OR

DISPLAY

MEANING

FUNCTION

LED Display

TEMP status

Displays current water temperature or

setpoint.

RST

RESET Button

Resets the unit after an alarm condition.

UP Button

Increases the displayed temperature.

DOWN Button

Decreases the displayed temperature.

SET

SET Button

Used to access and store parameters in the

unit.

DIGITAL OVER-TEMPERATURE

ALARM SWITCH

ADJUSTABLE TEMPERATURE

LIMIT SWITCH

RESET BUTTON FOR MANUAL

TEMPERATURE LIMIT SWITCH

MANUAL TEMPERATURE LIMIT

SWITCH

FUEL SELECTOR SWITCH