Benchmark 1500DF - 2000DF Boilers

CHAPTER 3 – OPERATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 43 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

Table 3-4: Configuration Menu

Menu Item Display

Available Choices or Limits

Default

Minimum

Maximum

Internal Setpt

Lo Temp Limit

Hi Temp Limit

130°F

Unit Type

KC Boiler, KC Boiler LN,

BMK Boiler Std, BMK Boiler LN,

BMK Blr Std Dual, BMK Blr LN, KC

Water Heater,

KC Wtr Heater LN,

Innovation WH,

BMK Blr LN Dual

BMK Boiler LN

Unit Size
(Only the unit sizes

available for the Unit

Type will be displayed)

750 MBH, 800 MBH 1000 MBH,

1500 MBH, 2000 MBH,
2500 MBH, 3000 MBH,

6000 MBH

1500 MBH

or

2000 MBH

Fuel Type

Natural Gas or Propane

Natural Gas

Boiler Mode

Constant Setpoint,

Remote Setpoint,

Direct Drive,

Combination,

Outdoor Reset

Constant

Setpoint

Remote Signal

(If Mode = Remote

Setpoint, Direct Drive or

Combination)

4 – 20 mA/1 – 5V

0 -20 mA/0 – 5V

PWM Input (Legacy BMS), Network

4 – 20 mA,

1-5V

Outdoor Sensor

Enabled or Disabled

Disabled

*Bldg Ref Temp

(If Mode = Outdoor

Reset)

40°F

230°F

70°F

*Reset Ratio

(If Mode = Outdoor

Reset)

0.1

9.9

1.2

*System Start Tmp

(If Outdoor Sensor =

Enabled)

30°F

100°F

60°F

Setpt Lo Limit

40°F

Setpt Hi Limit

60°F

Setpt Hi Limit

Setpt Lo Limit

210°F

140°F

Temp Hi Limit

40°F

210°F

160°F

*NOTE

The Bldg Ref Temp and Reset Ratio Menu Items are only

displayed when the Outdoor Sensor is set to “Enabled”.