Benchmark 1500DF - 2000DF Boilers

CHAPTER 8 – TROUBLESHOOTING GUIDE

Page 114 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

TABLE 8-1: BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

SSOV

SWITCH OPEN

1.

Actuator not allowing for full

closure of gas valve.

2.

SSOV powered when it should

not be.

3.

Defective Switch or Actuator.

4.

Incorrectly wired switch.

1.

Observe operation of the Safety Shut-Off Valve (SSOV)

through indicator on the Valve actuator and ensure that the

valve is fully and not partially closing.

2.

If the SSOV never closes, it may be powered continuously.

Close the gas supply and remove power from the unit.

Refer fault to qualified service personnel.

3.

Remove the electrical cover from the SSOV and check

switch continuity. If the switch does not show continuity

with the gas valve closed, either adjust or replace the

switch or actuator.

4.

Ensure that the SSOV Proof of Closure switch is correctly

wired.

STEPPER MOTOR

FAILURE

1.

Air/Fuel Valve out of calibration.

2.

Air/Fuel Valve unplugged.

3.

Loose wiring connection to the

stepper motor.

4.

Defective Air/Fuel Valve stepper

motor.

5.

Defective Power Supply Board or

fuse.

6.

Defective IGST Board.

1.

Refer to GF-112 (C-More O & M) and perform the Stepper

Feedback Calibration procedure in Section 6, section

6.2.1.

2.

Check that the Air/Fuel Valve is connected to the Control

Box.

3.

.Inspect for loose connections between the Air/Fuel Valve

motor and the wiring harness.

4.

Replace stepper motor.

5.

Check DS1 & DS2 LEDs on Power Supply Board. If they

are not steady ON, replace Power Supply Board.

6.

Check “Heartbeat” LED DS1 and verify it is blinking ON &

OFF every second. If not, replace IGST Board.