CHAPTER 9 – RS232 COMMUNICATION

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 119 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

Running a Command on a Remote Machine Using PuTTY – Continued

5.

You are now ready to execute this command on the remote machine, simply click

the Open button at the bottom of the dialog.

6.

You will have to provide an account name and password in the terminal window to

complete the process.

9.2 RS-232 COMMUNICATION SETUP

Regardless of the terminal emulation utilized, the following guidelines must be adhered to when

setting up the RS-232 communication link:

Baud Rate – The baud rates which can be used with the C-More Control Panel are:

o

2400

o

4800

o

9600 (Default)

o

19.2K

Data Format – The program must be set for:

o

8 data bits

o

1 stop bit

o

no parity

o

either Xon/Xoff or No flow control

9.3 MENU PROCESSING UTILIZING RS-232 COMMUNICATION

Viewing data logs and viewing or changing Control Panel menu options using RS-232

communication is accomplished as follows:

Menu Processing Utilizing Rs-232 Communication

1.

Start the emulator software program and ensure that the specified baud rate and data

formats have been entered.

2.

Press the Enter key on the laptop. An asterisk (*) prompt should appear.

3.

At the prompt, enter the valid RS-232 password (jaguar) in lower case letters and press

Enter.

4.

“Welcome to Aerco” will appear in the laptop or “dumb terminal” display with a listing of

the following available entry choices:

M

= Display next Menu

D

= Display menu items

N

= Display next menu items

Cxx

= Change item xx

F

= Fault log display

S

= Sensor log display

T

= Time line display

L

= Log off