7.8 AIR FILTER CLEANING & REPLACEMENT

The Benchmark boiler is equipped with an air filter (part no. 88014) which should be cleaned

and re-oiled every 12 months and replaced every 24 months. The air filter is located at the inlet

of the air fuel valve at the top of the boiler as shown in Figure 7-7.
To inspect/replace the air filter, proceed as follows:

Air Filter Cleaning & Replacement Procedures

1.

Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power

from the unit.

2.

Remove the top shroud from the unit by grasping the top handle and lifting straight up.

This will disengage the shroud from the four (4) pins in the side panels.

3.

Refer to Figure 7-7 and locate the air filter attached to the air/fuel valve inlet.

4.

Using a flat-tip screwdriver or 5/16” nut driver, loosen the clamp securing the filter to the

inlet flange of the air/fuel valve. Remove the filter and clamp.

5.

The filter may be cleaned in hot soapy water to remove oil and dirt. The filter should be

thoroughly dried and then sprayed with a light coating of oil, such as WD-40, prior to

reinstallation.

6.

Each replacement air filter is equipped with its own clamp. Therefore, simply install the

replacement air filter on inlet flange of the air fuel valve and tighten the clamp with a flat-

tip screwdriver or 5/16” nut driver.

7.

Replace the top shroud on the unit and return boiler to service use.

Figure 7-7: Air Filter Location

GAS

TRAIN

AIR FILTER

AIR FILTER

HOSE CLAMP

AIR/FUEL

VALVE