Appendix A: Boiler Menu Item Descriptions – Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU (Cont.)

Deadband High
Deadband Low

Deadband High and Deadband Low settings create an

“Outlet Temperature” Zone in which no Valve Position

corrections will be attempted.
The Deadband ZONE is defined as operating with an

Outlet Temperature between Active Setpoint +

Deadband High and Active Setpoint – Deadband Low.
When the Outlet Temperature reaches Active Setpoint

and remains there for a period of 15 seconds, the unit

will go into a DEADBAND MODE at which point no Valve

Position corrections will be attempted while the Outlet

Temperature remains anywhere within the Deadband

ZONE. When the unit is in the DEADBAND MODE, the

°F or °C LED will flash on and off. When the Outlet

Temperature drifts out of the Deadband ZONE, the

DEADBAND MODE will be terminated and the PID

LOOP will again attempt Valve Position corrections.
Setting range is 0 to 25. (Default is 2 for both Deadband

High and Deadband Low)

IGST Version

Displays the version of the IGST Board installed.

IGN Time Setting

Displays the MAX Ignition time of 4 Seconds or 7

Seconds as set in the Safety String Harness.

Slow Shutdown

Enables or Disables the slow shutdown feature. Default

is Disabled.

Slow Sht Duration

With the Slow Shutdown feature Enabled, sets the time a

boiler will continue to run at the Stop Level after running

above the Slow Sht Threshold level for 60 Seconds.
Span is 0 to 9999 Seconds, Default is 60 Seconds.

Slow Sht Threshold

Sets the Fire Rate above which a boiler will trigger the

Slow Shutdown feature.
Span is 40% to 100%, Default is 60%.