beautypg.com

12 combustion air, 1 combustion from outside the building, 2 combustion air from inside the building – AERCO BMK 2000DF User Manual

Page 32: 13 ducted combustion air

background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 2 – INSTALLATION

Page 32 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

For Massachusetts installations, the following companies provide vent systems which conform

to all applicable requirements for installations within the Commonwealth of Massachusetts.

Contact information is as follows:

Selkirk Corporation - Heatfab Division

130 Industrial Blvd.

Turners Falls, MA 01376

Phone: 1-800-772-0739

www.heat-fab.com

Watertown Supply

33Grove St.

Watertown, MA 02472

Phone: (617) 924-2840

http://www.watertownsupply.com/

M. A. Peacard

1250 Massachusetts Ave.

Boston MA 02125-1689

Phone: (617) 288-0629

www.mapeacard.com

Glover Sheet Meatal, Inc.

44 Riverdale Ave.

Newton, MA 02485

Phone: (617) 527-8178

www.gloversheetmetal.com

2.12 COMBUSTION AIR

The AERCO Benchmark Boiler Venting and Combustion Air Guide, GF-2050 MUST be

consulted before any flue or inlet air venting is designed or installed. Air supply is a direct

requirement of ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These codes should be

consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons or other chemicals that

can become hazardous when used in gas-fired equipment. Common sources of these

compounds are swimming pools, degreasing compounds, plastic processing, and refrigerants.

Whenever the environment contains these types of chemicals, combustion air MUST be

supplied from a clean area outdoors for the protection and longevity of the equipment and

warranty validation.
The more common methods of combustion air supply are outlined in the following sections. For

combustion air supply from ducting, consult the AERCO GF-2050, Gas Fired Venting and

Combustion Air Guide.

2.12.1 Combustion From Outside the Building

Air supplied from outside the building must be provided through two permanent openings. For

each unit these two openings must have a free area of not less than one square inch for each

4000 BTUs input of the equipment or 375 square inches of free area for the BMK 1500 or 500

square inches of free area for the BMK 2000. The free area must take into account restrictions

such as louvers and bird screens. For Canada installations, refer to the requirements specified

in CSA B149.1-10, sections 8.4.1 and 8.4.3.

2.12.2 Combustion Air from Inside the Building

When combustion air is provided from within the building, it must be supplied through two

permanent openings in an interior wall. Each opening must have a free area of not less than

one square inch per 1000 BTUH of total input or 3000 square inches of free area. The free area

must take into account any restrictions, such as louvers.

2.13 DUCTED COMBUSTION AIR

For ducted combustion air installations, the air ductwork must then be attached directly to the air

inlet connection on the sheet metal enclosure.

This manual is related to the following products: