beautypg.com

AERCO BMK 2000DF User Manual

Page 107

background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 8 – TROUBLESHOOTING GUIDE

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 107 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

TABLE 8-1: BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

DELAYED

INTERLOCK OPEN

1.

Delayed Interlock Jumper not

properly installed or missing.

2.

Device proving switch hooked to

interlocks is not closed.

1.

Check to insure jumper is properly installed across the delayed

interlock terminals in the I/O Box.

2.

If there are 2 external wires on these terminals, check to see if

an end switch for a proving device (such as a pump, louver,

etc.) is tied these interlocks. Ensure that the device and/or its

end switch is functional. A jumper may be temporarily installed

to test the interlock.

DIRECT DRIVE

SIGNAL FAULT

1.

Direct drive signal is not present:

--Not yet installed.

--Wrong polarity.

--Signal defective at source.

--Broken or loose wiring.

2.

Signal is not isolated (floating).

3.

Control Box signal type selection

switches not set for correct signal

type (voltage or current).

1.

Check I/O Box to ensure signal is hooked up.

--Hook up if not installed.

--If installed, check polarity.

--Measure signal level.

--Check wiring continuity between source and unit.

2.

Check signal at source to ensure it is isolated.

3.

Check DIP switch on PMC board to ensure it is set correctly for

the type of signal being sent. Check control signal type set in

Configuration Menu.

FLAME LOSS

DURING IGN

1.

Worn Flame Detector.

2.

No spark from Spark Igniter.

3.

Defective Ignition Transformer.

4.

Defective Ignition/Stepper (IGST)

Board.

5.

Defective SSOV.

1.

Remove and inspect the Flame Detector for signs of wear.

Replace if necessary.

2.

Close the internal gas valve in the unit. Install and arc a spark

igniter outside the unit.

3.

If there is no spark, check for 120VAC at the primary side to the

ignition transformer during the ignition cycle.

4.

If 120VAC is not present, the IGST Board in the Control Box

may be defective. Refer fault to qualified service personnel.

5.

While externally arcing the spark igniter, observe the open/close

indicator in the Safety Shut-Off Valve to ensure it is opening. If

the valve does not open, check for 120VAC at the valve input

terminals. If 120VAC is not present, the IGST board in the

Control Box may be defective. Refer fault to qualified service

personnel.

This manual is related to the following products: