Appendix E: RECOMMENDED PERIODIC TESTING

WARNING

Periodic testing of all boiler controls and safety devices is required to determine that they are

operating as designed. Precautions shall be taken while tests are being performed to protect

against bodily injury and property damage. The owner or user of an automatic boiler system

should set up a formal system of periodic preventive maintenance and testing. Tests should be

conducted on a regular basis and the results recorded in a log-book.

Item

Frequency

Accomplished

By

Remarks

Refer to indicated sections of this manual for detailed procedures

Gauges, monitors and

indicators

Daily

Operator

Visual inspection and record readings in operator log

Instrument and

equipment settings

Daily

Operator

Visual check against factory recommended

specifications

Weekly

Operator

Verify factory settings

Firing Rate Control

Semi-Annually Service Technician Verify factory settings

Annually

Service Technician Check with combustion calibration test equipment.

See sections 4.3 and 7.4.

Flue, vent, stack or

intake air duct

Monthly

Operator

Visually inspection condition and check for

obstructions

Spark Igniter-Injector

Weekly

Operator

See section 7.2

Air/Fuel Valve position

Weekly

Operator

Check position indicator dial (section 3.10)

SSOV Leakage test

Annually

Service Technician Check for leakage in accordance with the SSOV

manufacturer’s (Siemens) recommendations.

Flame failure

Weekly

Operator

Close manual gas shutoff valve and check safety

shutdown. See section 6.7

Flame signal strength

Weekly

Operator

Check flame strength using the Control Panel

Operating Menu. See section 3.4.

Low water level cut off

and alarm

Weekly

Operator

See section 6.4

Slow drain test

Semi-Annually

Operator

Perform a slow drain test in accordance with ASME

Boiler and Pressure Vessel Code,

Section IV.

High water temperature

safety control test

Annually

Service Technician See section 6.5

Operating controls

Annually

Operator

See section 3.2

Low air flow

Monthly

Operator

See section 6.8

High and low gas

pressure interlocks

Monthly

Operator

See sections 6.2 and 6.3

Air/Fuel Valve purge

position switch

Annually

Service Technician See section 6.10

Air/Fuel Valve ignition

position switch

Annually

Service Technician See section 6.11

Safety valves

As required

Operator

Check per A.S.M.E. Boiler and Pressure Vessel

Code, Section IV

Inspect burner

components

Semi-Annually Service Technician See section 7.6

Condensate Trap

Semi-

Annually

Operator

See section 7.7

Oxygen (O

2

) Level

Monthly

Operator

Verify oxygen level is between 3% and 8% during

boiler operation