Benchmark 1500DF - 2000DF Boilers

CHAPTER 3 – OPERATION

Page 50 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

c. The VALVE POSITION bargraph will show 100%.

Figure 3-4: Air/Fuel Valve In Purge Position

4.

Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will

show Purging and indicate the elapsed time of the purge cycle in seconds.

Figure 3-5: Blower Proof Switch

5.

Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the

following events occur:
(a) The Air/Fuel Valve rotates to the low-fire (Ignition Position) position and closes the

ignition switch. The Dial on the Air/Fuel Valve (Figure 3-6) will read between 25 and
35

to indicate that the valve is in the low fire position.

STEPPER
MOTOR

TO BLOWER

AIR IN

PURGE

VALVE POSITION

DIAL AT 100%

AIR/FUEL VALVE
OUTLET TO BLOWER

BLOCKED

INLET

SWITCH

BLOWER

PROOF

SWITCH

AIR/FUEL VALVE
INLET FROM GAS
TRAIN