Benchmark 1500DF - 2000DF Boilers

CHAPTER 2 – INSTALLATION

Page 30 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

When 0-10VDC is selected, the voltage output is used by the controller to modulate the

combustion blower via the I/O Box terminals labeled VFD/Blower (Section 2.10.11).

If On Board Boiler Sequencing Technology (BST) is enabled, the Analog Output

terminals are used to drive the isolation valve, open and closed.

When the 4-20mA is selected for the Analog Output, the 0-10VDC is disabled at the

VFD/Blower terminals, and the selected output is available at the terminals labeled

Analog Output +/-.

2.10.9 RS-485 Comm (+, GND, & -)

The RS-485 communication terminals are used when the boiler plant is being controlled by an

Energy Management System (EMS) or an AERCO Control System (ACS) using Modbus (RS-

485) communication.

2.10.10 RS-232 Comm (TxD & RxD)

The RS-232 communication terminals permit a laptop computer or other suitable terminal to be

connected to the boiler. The RS-232 communication feature permits viewing or changing of

Control Panel menu options and also provides access to data logs showing fault and sensor log

displays.

2.10.11 VFD/Blower (0-10 & AGND)

These terminals (0-10 & AGND) send an analog signal to control the blower speed. When any

of the 4-20mA options is selected for the Analog Outputs (Section 2.10.8), the output from the

VFD/Blower terminals is disabled.

2.10.12 Interlocks

The unit offers two interlock circuits for interfacing with Energy Management Systems and

auxiliary equipment such as pumps or louvers or other accessories. These interlocks are called

the Remote Interlock and Delayed Interlock (REMOTE INTL’K IN and DELAYED INTL’K IN in

Figure 2-12). Both interlocks, described below, are factory wired in the closed position (using

jumpers).

NOTE

Both the Delayed Interlock and Remote Interlock must be in the

closed position for the unit to fire.

2.10.12.1

Remote Interlock In (OUT & IN)

The remote interlock circuit is provided to remotely start (enable) and stop (disable) the unit

if desired. The circuit is 24 VAC and comes factory pre-wired closed (jumped).

2.10.12.2

Delayed Interlock In (OUT & IN)

The Delayed Interlock terminals can be used in one of two ways:

In conjunction with the optional external sequencing valve (see section 2.14 and

Chapter 10 – BST), a component of AERCO’s on-board Boiler Sequencing

Technology (BST) solution. By default a cable of the boiler’s wiring harness is

connected to these terminals. If BST is implemented, the other end of that cable is

connected to the sequencing valve.