beautypg.com

AERCO BMK 2000DF User Manual

Page 106

background image

Benchmark 1500DF - 2000DF Boilers

CHAPTER 8 – TROUBLESHOOTING GUIDE

Page 106 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

TABLE 8-1: BOILER TROUBLESHOOTING – Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT

DURING PURGE

1.

Blower not running or running too

slow.

2.

Defective Blocked Inlet switch.

3.

Blockage in air filter or Blocked

Inlet switch.

4.

Blocked blower inlet or inlet

ductwork.

5.

No voltage to Blocked Inlet switch

from C-More Control Box.

6.

PROBABLE CAUSES from 3 to 12

for AIRFLOW FAULT DURING

IGNITION apply for this fault.

1.

Start the unit. If the blower does not run check the blower solid

state relay for input and output voltage. If the relay is OK, check

the blower.

2.

Start the unit. If the blower runs, turn off unit and check the

Blocked Inlet switch for continuity. Replace the switch if

continuity does not exist.

3.

Remove the air filter and Blocked Inlet switch and inspect for

signs of blockage. Clean or replace as necessary.

4.

Inspect the inlet to the combustion blower including any

ductwork leading up to the combustion blower for signs of

blockage.

5.

During the start sequence, verify that 24 VAC is present

between each side of the switch and ground. If 24 VAC is not

present, refer fault to qualified service personnel.

6.

See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW

FAULT DURING IGNITION.

AIRFLOW FAULT

DURING RUN

1.

Blower stopped running due to

thermal or current overload.

2.

Blocked Blower inlet or inlet

ductwork.

3.

Blockage in air filter or Blocked

Inlet switch.

4.

Defective Blocked Inlet switch.

5.

Combustion oscillations.

6.

Probable causes from 3 to 16 for

AIRFLOW FAULT DURING

IGNITION applies for this fault.

1.

Check combustion blower for signs of excessive heat or high

current draw that may trip thermal or current overload devices.

2.

Inspect the inlet to the combustion blower, including any

ductwork leading up to the combustion blower, for signs of

blockage.

3.

Remove the air filter and Blocked Inlet switch and inspect for

signs of blockage, clean or replace as necessary.

4.

Verify that 24 VAC is present between each side of the switch

and ground. If 24 VAC is not present at both sides, replace

switch.

5.

Run unit to full fire. If the unit rumbles or runs rough, perform

combustion calibration.

6.

See CORRECTIVE ACTIONS from 3 to 12 for AIRFLOW

FAULT DURING IGNITION.

This manual is related to the following products: