beautypg.com

Appendix b: startup, status & display messages, Appendix b, Startup, status & display messages – AERCO BMK 2000DF User Manual

Page 145

background image

Benchmark 1500DF - 2000DF Boilers

APPENDIX B – STARTUP, STATUS & DISPLAY MESSAGES

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 145 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

Appendix B: STARTUP, STATUS & DISPLAY MESSAGES

Table B-1: Startup And Status Messages

MESSAGE

DESCRIPTION

DEMAND DELAY

XX sec

Displayed if Demand Delay is active.

DISABLED

HH:MM pm, pm

MM/DD/YY

Displayed if ON/OFF switch is set to OFF. The display also

shows the time (am or pm) and date that the unit was

disabled.

FLAME PROVEN

Displayed after flame has been detected for a period of 2

seconds. Initially, the flame strength is shown in %. After 5

seconds has elapsed, the time and date are shown in place

of flame strength.

IGNITION TRIAL

XX sec

Displayed during ignition trial of startup sequence. The

duration of cycle counts up in seconds.

PURGING

XX sec

Displayed during the purge cycle during startup. The

duration of the purge cycle counts up in seconds.

STANDBY

Displayed when ON/OFF switch is in the ON position, but

there is no demand for heat. The time and date are also

displayed.

WAIT

Prompts the operator to wait.

WARMUP

XX sec

Displayed for 2 minutes during the initial warm-up only.