CHAPTER 4 – INITIAL START-UP

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 67 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

Perform the following steps to check or adjust the digital alarm switch settings:

Digital Alarm Settings

1. Set the ON/OFF to the ON position.
2. Press the SET button on the Digital Alarm Switch. SP will appear in the display.
3. Press the SET button again. The current over-temperature limit value stored in memory will

be displayed. (default = 210°F).

4. If the display does not show the required over-temperature alarm setting, press the ▲ or ▼

arrow button to change the display to the desired temperature setting.

5. Once the desired over-temperature alarm setting (210ºF) is displayed, press the SET button

to store the setting in memory.

6. To calibrate the offset (P1), press and hold the SET button for 8 seconds on the Digital

Alarm Switch. Access code value 0 should appear in the display. The switch comes from the

factory with the code set at 0. AERCO recommends that you do not change this code.

7. Press the SET button again to enter the code. The first parameter label (SP) will appear in

the display.

8. Using the ▲ and ▼ arrow keys, select parameter P1.
9. Press SET to view the value stored in memory.
10. If the desired value is not displayed, modify the setting using the ▲ and ▼ arrow keys. The

value can be changed from -10° to +10° offset. Press SET to enter the value and exit to the

text parameter.

11. To exit the programming mode, press the SET and ▼ buttons simultaneously, or simply wait

one minute and the display will automatically exit the programming mode.

12. Once the programming mode has been exited, the display will show the current outlet water

temperature of the boiler.