Benchmark 1500DF - 2000DF Boilers

APPENDIX A – BOILER MENU DESCRIPTIONS

Page 138 of 196

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0098_0A

04/01/2014

Ph.: 800-526-0288

GF-144

Appendix A: Boiler Menu Item Descriptions – Continued

MENU LEVEL & OPTION

DESCRIPTION

SETUP MENU

Password

Allows Level 1 or Level 2 password to be entered.
Entering the Level 1 Password (159) allows options in the

Setup, Configuration and Tuning Menus to be modified.
Entering the Level 2 Password (6817) allows options in the

Calibration and Diagnostics Menus to be changed or

activated, in addition to all Level 1 Menu options.

Language

Permits selection of English, Spanish or French for

displayed messages. Default is English.

Time

Displays time from 12:00 am to 11:59 pm.

Date

Displays dates from 01/01/00 to 12/31/99

Unit of Temp

Permits selection of temperature displays in degrees

Fahrenheit (°F) or degrees Celsius (°C). Default is °F.

Comm Address

For RS-485 communications (0 to 127). Default address is

0. RS-232 should have its own (programmable) password.

Baud Rate

Allows communications Baud Rate to be set (2400 to

19.2K). Default is 9600.

Min Upload Timer

Mandatory for AERCO OnAER Remote Data Collection

(ORDC). This parameter enables ORDC and defines the

minimum amount of time between heartbeat data uploads

in seconds. The COMM LED will light during the upload.

Unit Alpha

Mandatory for AERCO OnAER Remote Data Collection.

This value must match the first alpha digit on the Code

Plate, e.g., G-12-1234.

Unit Year

Mandatory for AERCO OnAER Remote Data Collection.

This value must match the 2-digit year on the Code Plate,

e.g., G-12-1234.

Unit Serial #

Mandatory for AERCO OnAER. Remote Data Collection.

This value must match the 4-digit serial # on the Code

Plate, e.g., G-12-1234.

Software Version

Identifies the current software version of the control box

(Ver 0.0 to Ver 9.9).

Internal Setpoint

Allows internal setpoint to be set. Default is 130°F.

Unit Type

Allows selection of KC Boiler, KC Boiler LN, BMK Boiler

Std, BMK Blr Std Dual, BMK Boiler LN, BMK Blr LN Dual,

KC Water Heater, KC Wtr Heater LN, Innovation WH