AERCO BMK 2000DF User Manual
Page 138

Benchmark 1500DF - 2000DF Boilers
APPENDIX A – BOILER MENU DESCRIPTIONS
Page 138 of 196
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
OMM-0098_0A
04/01/2014
Ph.: 800-526-0288
GF-144
Appendix A: Boiler Menu Item Descriptions – Continued
MENU LEVEL & OPTION
DESCRIPTION
SETUP MENU
Password
Allows Level 1 or Level 2 password to be entered.
Entering the Level 1 Password (159) allows options in the
Setup, Configuration and Tuning Menus to be modified.
Entering the Level 2 Password (6817) allows options in the
Calibration and Diagnostics Menus to be changed or
activated, in addition to all Level 1 Menu options.
Language
Permits selection of English, Spanish or French for
displayed messages. Default is English.
Time
Displays time from 12:00 am to 11:59 pm.
Date
Displays dates from 01/01/00 to 12/31/99
Unit of Temp
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C). Default is °F.
Comm Address
For RS-485 communications (0 to 127). Default address is
0. RS-232 should have its own (programmable) password.
Baud Rate
Allows communications Baud Rate to be set (2400 to
19.2K). Default is 9600.
Min Upload Timer
Mandatory for AERCO OnAER Remote Data Collection
(ORDC). This parameter enables ORDC and defines the
minimum amount of time between heartbeat data uploads
in seconds. The COMM LED will light during the upload.
Unit Alpha
Mandatory for AERCO OnAER Remote Data Collection.
This value must match the first alpha digit on the Code
Plate, e.g., G-12-1234.
Unit Year
Mandatory for AERCO OnAER Remote Data Collection.
This value must match the 2-digit year on the Code Plate,
e.g., G-12-1234.
Unit Serial #
Mandatory for AERCO OnAER. Remote Data Collection.
This value must match the 4-digit serial # on the Code
Plate, e.g., G-12-1234.
Software Version
Identifies the current software version of the control box
(Ver 0.0 to Ver 9.9).
Internal Setpoint
Allows internal setpoint to be set. Default is 130°F.
Unit Type
Allows selection of KC Boiler, KC Boiler LN, BMK Boiler
Std, BMK Blr Std Dual, BMK Boiler LN, BMK Blr LN Dual,
KC Water Heater, KC Wtr Heater LN, Innovation WH