AERCO BMK 2000DF User Manual
Page 147

Benchmark 1500DF - 2000DF Boilers
APPENDIX B – STARTUP, STATUS & DISPLAY MESSAGES
OMM-0098_0A
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 147 of 196
GF-144
Ph.: 800-526-0288
04/01/2014
Table B-2: Fault Messages – Continued
FAULT MESSAGE
FAULT DESCRIPTION
LOW WATER
LEVEL
The Low Water Cutoff board is indicating low water level.
NETWORK COMM
FAULT
The RS-485 network information is not present or is
corrupted.
O
2
% OUT OF RANGE The
O
2
% has gone below 3% or above 8%.
OUTDOOR TEMP
SENSOR FAULT
The temperature measured by the Outdoor Air Sensor is out
of range.
OUTLET TEMP
SENSOR FAULT
The temperature measured by the Outlet Sensor is out of
range:
•
OUTLET TEMPERATURE display = SHt Indicates
sensor is shorted
•
OUTLET TEMPERATURE display = Opn indicates
sensor is open-circuited
PRG SWTCH CLOSED
DURING IGNITION
The Purge Position Limit Switch on the Air/Fuel Valve closed
during ignition.
PRG SWTCH OPEN
DURING PURGE
The Purge Position Limit Switch on the Air/Fuel Valve
opened during purge.
REMOTE SETPT
SIGNAL FAULT
The Remote Setpoint signal is not present or is out of range.
RESIDUAL
FLAME
The Flame signal was seen for more than 60 seconds during
standby.
SSOV
SWITCH OPEN
The SSOV switch opened during standby.
SSOV FAULT
DURING PURGE
The SSOV switch opened during purge.
SSOV FAULT
DURING IGN
The SSOV switch closed or failed to open during ignition.
SSOV FAULT
DURING RUN
The SSOV switch closed for more than 15 seconds during
run.
SSOV RELAY
FAILURE
A failure has been detected in one of the relays that control
the SSOV.
STEPPER MOTOR
FAILURE
The Stepper Motor failed to move the Air/Fuel Valve to the
desired position.