Benchmark 1500DF - 2000DF Boilers

APPENDIX D – BOILER DEFAULT SETTINGS

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 151 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

Appendix D: BOILER DEFAULT SETTINGS

Appendix D: Boiler Default Settings

MENU & OPTION

FACTORY DEFAULT

Setup Menu

Password

0

Language

English

Unit of Temp

Fahrenheit

Comm Address

0

Baud Rate

9600

Configuration Menu

Internal Setpt

130°F

Unit Type

BMK Boiler LN

Unit Size

1500 MBH or 2000 MBH

Fuel Type

Natural Gas

Boiler Mode

Constant Setpoint

Remote Signal (If Mode = Remote Setpoint,

Direct Drive or Combination)

4 – 20 mA / 1-5V

Bldg Ref Temp

(If Boiler Mode = Outdoor Reset)

70°F

Reset Ratio

(If Boiler Mode = Outdoor Reset)

1.2

Outdoor Sensor

Disabled

System Start Tmp

(If Outdoor Sensor = Enabled)

60°F

Setpt Lo Limit

60°F

Setpt Hi Limit

195°F

Temp Hi Limit

195°F

Max Valve Position

100%

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V

CAUTION: DO NOT Change

Lo Fire Timer

2 sec