Appendix d: boiler default settings, Appendix d, Boiler default settings – AERCO BMK 2000DF User Manual
Page 151

Benchmark 1500DF - 2000DF Boilers
APPENDIX D – BOILER DEFAULT SETTINGS
OMM-0098_0A
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Page 151 of 196
GF-144
Ph.: 800-526-0288
04/01/2014
Appendix D: BOILER DEFAULT SETTINGS
Appendix D: Boiler Default Settings
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
BMK Boiler LN
Unit Size
1500 MBH or 2000 MBH
Fuel Type
Natural Gas
Boiler Mode
Constant Setpoint
Remote Signal (If Mode = Remote Setpoint,
Direct Drive or Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit
60°F
Setpt Hi Limit
195°F
Temp Hi Limit
195°F
Max Valve Position
100%
Pump Delay Timer
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
Analog Output
Valve Position 0-10V
CAUTION: DO NOT Change
Lo Fire Timer
2 sec