Appendix A: BOILER MENU ITEM DESCRIPTIONS

MENU LEVEL & OPTION

DESCRIPTION

OPERATING MENU

Active Setpoint

This is the setpoint temperature to which the

control is set when operating in the Constant

Setpoint, Remote Setpoint or Outdoor Reset

Mode. When in the Constant Setpoint Mode, this

value is equal to the Internal Setpoint setting in the

Configuration Menu. When in the Remote

Setpoint Mode, this value is the setpoint equivalent

to the remote analog signal supplied to the unit.

When in the Outdoor Reset Mode, this is the

derived value from the charts in Appendix F.

Inlet Water Temp

Displays the inlet water temperature in °F.

Air Temp

Air Temp is the air temperature at the input to the

Air/Fuel Valve. This reading is one of the

parameters used to control the Blower Motor

speed.

Outdoor Temp

Displayed only if outdoor sensor is installed and

enabled.

Valve Position In

Desired input valve position. This would normally

be the same as the fire valve position shown on

the bargraph (valve position out) when the boiler is

operating.

Exhaust Temp

Displays the exhaust temperature (°F)

Flame Strength

Displays flame strength from 0% to 100%.

Oxygen Level

Displays the real-time combustion oxygen (O

2

)

level (%) measured by the O

2

sensor.

Run Cycles

Displays the total number of run cycles from 0 to

999,999.

Run Hours

Displays total run time of unit in hours from 0 to

9,999,999.

Fault Log

Displays information on the last 20 faults.