Appendix A: Boiler Menu Item Descriptions – Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU (Cont.)

Aux Start On Dly

Specifies the amount of time to wait (0 to 120 sec.)

between activating the Aux Relay (due to a demand)

and checking the pre-purge string to start the boiler.

Default is 0 sec.

Failsafe Mode

Allows the Failsafe mode to be set to either Constant

Setpoint or Shutdown. Default is Shutdown.

Analog Output

Must be set to Valve Pos 0-10V for BMK 1500 & 2000.

Lo Fire Timer

Specifies how long (2 to 600 sec.) to remain in the low

fire position after ignition, before going to the desired

output. Default is 2 sec.

Setpt Limiting

Setpoint Limiting can be Enables or Disablled. The

default setting is Enabled.

Setpt Limit Band

The Setpoint Limit Band can be set from 0 to 10. The

default setting is 5.

Network Timeout

Specifies the timeout value (seconds) before a

Modbus fault is declared. Available settings range from

5 to 999 seconds. Default is 30 seconds.

Shutoff Dly Temp

This feature delays the shutdown of a boiler in order to

reduce excessive cycling. This specifies the

temperature value the Outlet Temperature is permitted

to rise above setpoint before being shut down.
Span is 0 to 25, Default is 10.

Demand Offset

This entry will reduce excessive ON/OFF cycling in

AUTO mode. When this entry is a non-zero value, the

unit will not turn on again until Valve Position In

reaches the Start Level value AND the Outlet

Temperature goes below the Active Setpoint –
Demand Offset.

In addition, the boiler will fire at the

29% Valve Position level or below for a period of one

minute.
When this entry is set to zero, the unit will turn on

again as soon as the Valve Position in reaches the
Start Level

value. There will not be a one minute delay

when firing at the 29% Valve Position level.
Setting range is 0 to 25. (Default is 10)