APPENDIX A – BOILER MENU DESCRIPTIONS

OMM-0098_0A

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 139 of 196

GF-144

Ph.: 800-526-0288

04/01/2014

Appendix A: Boiler Menu Item Descriptions – Continued

MENU LEVEL & OPTION

DESCRIPTION

CONFIGURATION MENU

Internal Setpoint

Allows internal setpoint to be set (40°F to 240°F). Default is

130°F.

Unit Size

Sets unit size from 600 MBH to 6000 MBH depending on the

Unit Type.

Fuel Type

Allows selection of Natural Gas or Propane

Boiler Mode

(If Unit Type = Boiler)

It allows selection of: Constant Setpoint, Remote Setpoint,

Direct Drive, Combination, or Outdoor Reset Mode. Default

is Constant Setpoint Mode.

Remote Signal
(If Mode = Remote Setpoint,

Direct Drive or Combination)

Used to set the type of external signal which will be used

when operating in the Remote Setpoint, Direct Drive or

Combination Mode. The factory default is 4-20 mA/1-5V.

Bldg Ref Temp
(If Boiler Mode = Outdoor

Reset)

Allows the building reference temperature to be set when

operating a boiler in the Outdoor Reset Mode. Default is

70°F.

Reset Ratio
(If Boiler Mode = Outdoor

Reset)

Permits setting of Reset Ratio when operating boiler in the

Outdoor Reset Mode. Reset Ratio is adjustable from 0.1 to

9.9. Default is 1.2.

Outdoor Sensor

Allows outdoor sensor function to be enabled or disabled.

Default is disabled.

System Start Tmp
(If Outdoor Sensor is Enabled)

If outdoor sensor is enabled, this menu item allows the

system start temperature to be set from 30 to 100°F.

Default is 60°F.

Setpoint Lo Limit

Used to set the minimum allowable setpoint (40°F to

Setpoint Hi Limit). Default is 60°F

Setpoint Hi Limit

Used to set the maximum allowable setpoint (Setpoint Lo

Limit to 210°F). Default is 140°F.

Temp Hi Limit

This is the maximum allowable outlet temperature (40 to

210°F). Any temperature above this setting will turn off the

unit. The temperature must then drop 5° below this setting to

allow the unit to run. Default Hi Limit is 160°F.

Max Valve Position

Sets the maximum allowable valve position for the unit (40%

to 100%). Default is 100%.

Pump Delay Timer

Specifies the amount of time (0 to 30 min.) to keep the pump

running after the unit turns off. Default is zero.