Full auto calibration, Full auto calibration -14 – KEYENCE LV-N10 Series User Manual

Page 38

background image

3-3 Adjusting the Sensitivity

3

Ba
sic
Oper

ati
on

3-14

- Digital Laser Sensor LV-N10 Series User's Manual -

This method automatically sets sensitivity using a moving workpiece.
Sensitivity can be easily set by passing a workpiece without shutting down operating
equipment.

1

While the workpiece passes through,
press and hold the [SET] button until
"
SEt" flashes.

2

After the workpiece has completely
passed through, release the [SET] but-
ton.
Calibration is complete after the setting
value flashes momentarily, and then
stops (lights up).

• If detection is not stable after the setting operation, for example due to

vibration, press the

button to adjust the setting value.

• When performing two-point calibration on channel 2 of the 2-output type,

set the channel switch to "2".

Full Auto Calibration

Reference

Setting
value

MAX

MIN

Time

Receiv

ed

lig

ht intensity

The setting value is determined
as the middle value between the
maximum and minimum light
intensity received values
obtained while holding down the
[SET] button.

1

2