Technical data
General data and operating conditions
3.1
l
3.1−1
EDSVS9332S EN 6.0−07/2013
3.1
General data and operating conditions
Conformity and approval
Conformity
CE
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMC Directive
Approval
UL
cULus
Power Conversion Equipment (File No. E132659)
Protection of persons and equipment
Type of protection
EN 60529
IP20
IP41 in case of thermally separated installation
(push−through technique) between the control
cabinet (inside) and the environment.
NEMA 250
Protection against accidental contact in accordance
with type 1
Earth leakage current IEC/EN 61800−5−1 > 3.5 mA
Observe regulations and
safety instructions!
Insulation of control
circuits
EN 61800−5−1
Safe mains isolation by double (reinforced)
insulation for terminals X1 and X5.
Basic insulation (single isolating distance) for
terminals X3, X4, X6, X7, X8, X9, X10 and X11.
Insulation resistance
IEC/EN 61800−5−1 < 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Protective measures
Against short circuit, earth fault (earth−fault
protected during mains connection, limited
earth−fault protection during operation),
overvoltage, motor overtemperature (input for PTC
or thermal contact)
EMC
Noise emission
IEC/EN 61800−3
Cable−guided, up to 10 m motor cable length with
mains filter A: category C2.
Radiation, with mains filter A and installation in
control cabinet: category C2
Interference
immunity
IEC/EN 61800−3
Category C3
Ambient conditions
Climatic
Storage
IEC/EN 60721−3−1 1K3 (−25 ... +55 °C)
< 6 months
1K3 (−25 ... +40 °C)
> 6 months
> 2 years: anodise DC bus
capacitors
Transport
IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)
Operation
EVS9321 ...
EVS9326
IEC/EN 60721−3−3 3K3 (0 ... +55 °C)
> +40 °C: reduce the rated output current by
2.5 %/°C.
EVS9327 ...
EVS9332
3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by
2.5 %/°C.
Pollution
EN 61800−5−1
Degree of pollution 2
General data
Operating conditions