Wiring of the standard device – Lenze EVS9332xS User Manual
Page 123

Wiring of the standard device
Standard devices with a power of 45 kW
Mains connection, DC supply
5.6
5.6.3
l
5.6−4
EDSVS9332S EN 6.0−07/2013
PE
+UG
-UG
L1
L2
L3
3
0
1
2
L1, L2, L3
+U , -U
PE
G
G
M8
15 Nm
132 lb-in
}
+
PE
9300vec126
Fig. 5.6−2
Mains connection, DC supply for 45 kW controller
0 PE stud
Connect PE cable with ring cable lug
1 Conductive surface
2 Shield clamp
Place shield with large surface on control cabinet mounting plate and fasten
with shield clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also place the shield on the PE stud
3 Mains and DC bus connection
L1, L2, L3: Connection of mains cable with ring cable lugs
+U
G
, −U
G
: Connection of DC−bus components or connection of the controller
in the DC−bus system (see system manual)