Monitoring, Fault responses, Configuration – Lenze EVS9332xS User Manual
Page 228: Danger, Stop
Configuration
Monitoring
Fault responses
8.2
8.2.1
l
8.2−1
EDSVS9332S EN 6.0−07/2013
8.2
Monitoring
Different monitoring functions (
¶ 8.31) protect the drive system from
impermissible operating conditions.
If a monitoring function responds,
ƒ the set fault response is triggered to protect the drive and
ƒ the fault message is entered position 1 in the fault history buffer
(C0168/x, in case of ECSxP: C4168/x) (
¶ 9.2−1).
8.2.1
Fault responses
Depending on the failure, one or more of the following responses are
possible:
Response
Effects on the drive and controller
Danger warnings
TRIP
(highest
priority)
l
Switches the power outputs U, V, W to a high
resistance until TRIP is reset
l
The drive coasts (no control!).
l
After TRIP reset, the drive accelerates to its
setpoint on the ramps set.
Message
Switches the power outputs U, V, W to a high
resistance as long as the message is active.
}
Danger!
The drive restarts
automatically if the message
is no longer available.
l
Short−
time
messa
ge
£ 0.5 s
The drive coasts (no control) as long as
the message is active.
If the message is no longer available,
the drive accelerates to its setpoint
with maximum torque.
l
Longer
messa
ge
> 0.5 s
The drive coasts (due to internal
controller inhibit) as long as the
message is active.
If required, restart the drive.
Warning
l
Only display of the failure.
l
The drive operates in a controlled manner.
(
Stop!
As these responses have no
effect on the drive behaviour,
the drive can be destroyed.
Off
l
No response on failures! Monitoring is
deactivated.