Configuration, Code table – Lenze EVS9332xS User Manual
Page 249

Configuration
Code table
8.4
l
8.4−8
EDSVS9332S EN 6.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0116
s
® Selection list 2 Signal configuration of the free digital
outputs
Free digital outputs can only be evaluated
when they are linked to automation
interfaces.
1 FDO−00
1000 FIXED0
... ...
...
...
32 FDO −31
1000 FIXED0
C0117
s
®
® Selection list 2 Signal configuration DIGOUT
à
Depending on C0005
1 DIGOUT1
15000 DCTRL−TRIP
X5/A1
2 DIGOUT2
10650 CMP1−OUT
X5/A2
3 DIGOUT3
500
DCTRL−RDY
X5/A3
4 DIGOUT4
5003 MCTRL−MMAX
X5/A4
C0118
0
1
HIGH active
LOW active
Terminal polarity DIGOUT
1 DIGOUT1 POL
1
X5/A1
2 DIGOUT2 POL
1
X5/A2
3 DIGOUT3 POL
0
X5/A3
4 DIGOUT4 POL
0
X5/A4
C0120 OC6 LIMIT
0
00
{1 %}
120 Threshold for the I
2
× t monitoring (motor).
l
0 = I
2
× t monitoring switched off
l
I
2
× t > C0120
ð trip OC6
C0121 OH7 LIMIT
150
45
{1 °C}
150 Temperature for OH7
Threshold for motor temperature warning
C0122 OH4 LIMIT
85
45
{1 °C}
85 Temperature for OH4
Warning threshold − heatsink temperature
C0125 BAUD RATE
0
0
1
2
3
4
9600 baud
4800 baud
2400 baud
1200 baud
19200 baud
LECOM baud rate
LECOM baud rate for 2102 accessory module
C0126 MONIT CE0
3
0
2
3
TRIP
Warning
Off
CE0monitoring
Configuration of communication error
monitoring with CE0 automation interface
C0127 OC8 LIMIT
0
0
{1 %}
120 Threshold for the I
2
× t advance warning
(motor).
l
0 = I
2
× t warning switched off
l
I
2
× t > C0127
ð OC8 fault message
(response set in C606)
C0128 TAU MOTOR
5.0
0.1
{0.1 min}
50.0 Thermal time constant of the motor
The time constant is required for calculating
the I
2
× t disconnection.
C0130 ACT TI
g
NSET
Active T
i
times of NSET
C0134 RFG CHARAC
0
0
1
Linear
S−shaped
NSET
Ramp function generator characteristic for
main setpoint
C0135 CONTROL
WORD
0
0
{1}
65535 Control word
Device control word for LECOM−A/B/LI or
keypad.
C0136
g
1 CTRLWORD
C135
Control word C135
2 CTRLWORD
CAN
Control word CAN
3 CTRLWORD AIF
Control word AIF