Configuration – Lenze EVS9332xS User Manual
Page 251
Configuration
Code table
8.4
l
8.4−10
EDSVS9332S EN 6.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0169
g corresponding mains switch−on time
List of the times when the faults occurred
under C0168 (based on C0179)
1 FAILTIME ACT
Currently active fault
2 FAILTIME OLD1
Last fault
... ...
...
8 FAILTIME OLD7
Last but six fault
C0170
g corresponding mains switch−on time
List of how often the faults have occurred
consecutively under C0168
History buffer
1 COUNTER ACT
Currently active fault
2 COUNTER
OLD1
Last fault
... ..
...
8 COUNTER
OLD7
Last but six fault
C0172
s
OV REDUCE
0
0
{10 V}
100 OV reduce
Threshold for activating the brake torque
reduction before OU message
C0173
s
UG LIMIT
1
DC−bus voltage thresholds
Check during commissioning and adapt if
necessary!
All drive components in the interconnection
must have the same thresholds!
0
Mains<400V +−brake LU=285V,
OU=770V−755V
Operation on mains <400 V with or without
braking unit
1
Mains=400V +−brake LU=285V,
OU=770V−755V
Operation on 400 V mains with or without
braking unit
2
Mains=460V +−brake LU=328V,
OU=770V−755V
Operation on 460 V mains with or without
braking unit
3
Mains=480V −brake LU=342V,
OU=770V−755V
Operation on 480 V mains without braking
unit
4
Mains=480V +−brake LU=342V,
OU=800V−785V
Operation on 480 V mains with braking unit
C0178 OP TIMER
g 0
{1 s}
4294967295 Elapsed−time meter
l
Time when the controller was enabled
C0179 MAINS TIMER
g 0
{1 s}
4294967295 Power−on time meter
l
Time during which the mains was
switched on
C0182 TI S−SHAPED
20.00 0.01
{0.01 s}
50.00 NSET
T
i
time of the S−shaped ramp function
generator
(determines the shape of the S curve)
l
Low values
Þsmall S rounding
l
High values
Þlarge S rounding