Code table, Configuration – Lenze EVS9332xS User Manual
Page 242

Configuration
Code table
8.4
l
8.4−1
EDSVS9332S EN 6.0−07/2013
8.4
Code table
How to read the code table
Column
Abbreviation
Meaning
Code
Cxxxx
Code Cxxxx
l
Parameter value of the code can be defined
differently for each parameter set
l
Parameter value is accepted immediately (ONLINE)
1
Subcode 1 of Cxxxx
2
Subcode 2 of Cxxxx
v
Changed parameter of code or subcode is accepted after pressing
T V
s
Changed parameter of code or subcode is accepted after pressing
T V when
the controller is inhibited
Designation
Designation of the code
Lenze
Lenze setting (value at delivery or after restoring the delivery status with C0002)
à
The column "IMPORTANT" contains additional information
g
The code only displays a value. It cannot be configured.
Selection
1
{%}
99 Min. value
{unit}
max. value
IMPORTANT
−
Short, important explanation
Code
Possible settings
IMPORTANT
No.
Designation
Lenze Selection
C0002
s
PAR LOAD
0
Load parameter set
0
Default setting
Restore delivery status
1
2
3
4
Load parameter set 1
Load parameter set 2
Load parameter set 3
Load parameter set 4
Load and activate parameter set saved in the
controller
l
Parameter set 1 is loaded automatically
after every mains connection.
11
12
13
14
Load parameter set 1externally
Load parameter set 2 externally
Load parameter set 3 externally
Load parameter set 4externally
Load parameter set from the keypad in the
controllerand activate it
20
Load all parameter sets from the keypad in
the EEPROM of the controller.
l
The current parameter set in the RAM of
the controller is overwritten. Save the
parameter set.
C0003 PAR SAVE
0
Save parameter set
0
Executed
Saving completed
1
2
3
4
Save parameter set 1
Save parameter set 2
Save parameter set 3
Save parameter set 4
Save the parameters loaded in the controller
in the parameter set selected
11
Save all parameter sets into keypad
Copying parameter sets from the standard
device into the keypad XT
C0004 OP DISPLAY
56
0
{1}
1999 Status display
Keypad shows selected code in the operating
level if no other status messages from C0183
are active