Loading a parameter set, Parameter setting, Danger – Lenze EVS9332xS User Manual
Page 216
Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Loading a parameter set
7.2
7.2.5
l
7.2−7
EDSVS9332S EN 6.0−07/2013
7.2.5
Loading a parameter set
The keypad serves to load a saved parameter set into the main memory
when the controller is inhibited. After the controller is enabled, it operates
with the new parameters.
}
Danger!
ƒ
When a new parameter set is loaded, the controller is
reinitialised and acts as if it had been connected to the mains:
– System configurations and terminal assignments can be
changed. Make sure that your wiring and drive configuration
comply with the settings of the parameter set.
ƒ
Only use terminal X5/28 as source for the controller inhibit!
Otherwise the drive may start in an uncontrolled way when
switching over to another parameter set.
)
Note!
ƒ
After switching on the supply voltage, the controller always
loads parameter set 1 into the main memory.
ƒ
It is also possible to load other parameter sets into the main
memory via the digital inputs or bus commands.
Step
Key
sequence
Action
1.
Inhibit controller
Terminal X5/28 = LOW
2.
Load the saved parameter set
into the main memory
A
z y Z Y
Select the code C0002 "PAR LOAD" in the
menu "Load/Store"
B
V
Change to the parameter level
The active parameter set is displayed, e. g.
display "0" and "Load Default"
If you want to restore the delivery status,
proceed with D
Select the parameter set
to be loaded
C
z
Load parameter set 1:
ð Set "1" "Load PS1"
Load parameter set 2:
ð Set "2" "Load PS2"
Load parameter set 3:
ð Set "3" "Load PS3"
Load parameter set 4:
ð Set "4" "Load PS4"
D
T V
"RDY" goes off. The parameter set is loaded
completely into the main memory if "RDY"
is displayed again.
3.
Change to the code level
A
V
Display of the operating level
B
V
Display of C0002 "PAR LOAD"
4.
Enable controller
Terminal X5/28 = HIGH
The drive is running with the settings of
the loaded parameter set