Wiring of the standard device, Stop – Lenze EVS9332xS User Manual
Page 141
Wiring of the standard device
Control terminals
Important notes
5.8
5.8.1
l
5.8−2
EDSVS9332S EN 6.0−07/2013
1
2
0
9300vec129
Fig. 5.8−1
Connection of cable shield to shield sheet
0 Shield sheet
1 Fasten shield sheet with M4 × 10 mm screw at the bottom of the control
card
2 Securely clamp cable shield with lugs
(
Stop!
ƒ
Connect or disconnect the terminal strips only if the controller
is disconnected from the mains!
ƒ
Wire the terminal strips before connecting them!
ƒ
Unused terminal strips must also be plugged on to protect the
contacts.
Cable type
Wire end ferrule
Maximum cable
cross−section
Tightening
torque
Stripping
length
Rigid
—
2.5 mm
2
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
5 mm
Flexible
Without wire end
ferrule
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule
without plastic
sleeve
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule
with plastic sleeve
2.5 mm
2
(AWG 14)
How to connect the shield
Terminal data