Dc−bus operation – Lenze EVS9332xS User Manual
Page 339
DC−bus operation
Fuses and cable cross−sections
10.3
l
10.3−2
EDSVS9332S EN 6.0−07/2013
Inverter
DC fuse 14 × 51
(EFSGR0xx0AYHx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type
Mains
Rated current of fuse
Rated current of fuse
+U
G
, −U
G
Laying system
B2
C
[A]
[A]
[mm
2
]
[mm
2
]
EVS9321
3/PE
400 V
12
12
1.5
1.5
EVS9322
12
12
1.5
1.5
EVS9323
12
12
1.5
1.5
EVS9324
20
20
1.5
1.5
EVS9325
40
40
4.0
4.0
EVS9326
50
50
6.0
1)
4.0
1)
Pin−end connector required, since a maximum cable cross−section of 4 mm
2
can be connected to
the inverter.
Inverter
DC fuse NH1
(EFSGRxxx0ANVx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type
Mains
Rated current of fuse
Rated current of fuse
+U
G
, −U
G
Laying system
B2
C
[A]
[A]
[mm
2
]
[mm
2
]
EVS9327
3/PE
400 V
100
100
−
25
EVS9328
100
100
−
25
EVS9329
200
−
−
25
EVS9330
200
−
−
50
EVS9331
200
−
−
50
Inverter
DC fuse NH2
(EFSGRxxx0ANWx)
DC fuse 22 × 58
(EFSGR0xx0AYIx)
Installation in
accordance with
EN 60204−1
Type
Mains
Rated current of fuse
Rated current of fuse
+U
G
, −U
G
Laying system
B2
C
[A]
[A]
[mm
2
]
[mm
2
]
EVS9332
3/PE
400 V
250
−
−
95