Wiring of the standard device – Lenze EVS9332xS User Manual
Page 133

Wiring of the standard device
Standard devices in the power range 55 ... 75 kW
Mains connection, DC supply
5.7
5.7.3
l
5.7−4
EDSVS9332S EN 6.0−07/2013
PE
+UG
-UG
L1
L2
L3
3
0
1
2
L1, L2, L3
+U , -U
PE
G
G
M10
30 Nm
264 lb-in
}
+
PE
9300vec127
Fig. 5.7−2
Mains connection, DC supply for 55 ... 75 kW drive controller
0 PE stud
Connect PE cable with ring cable lug
1 Conductive surface
2 Shield clamp
Place shield with large surface on control cabinet mounting plate and fasten
with shield clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also place the shield on the PE stud
3 Mains and DC bus connection
L1, L2, L3: Connection of mains cable with ring cable lugs
+U
G
, −U
G
: Connection of DC−bus components or connection of the controller
in the DC−bus system (see system manual)