Mains choke/mains filter assignment, Wiring of the standard device – Lenze EVS9332xS User Manual
Page 102
Wiring of the standard device
Standard devices in the power range 0.37 ... 11 kW
Mains choke/mains filter assignment
5.4
5.4.5
l
5.4−7
EDSVS9332S EN 6.0−07/2013
Supply conditions
Range
Description
Fuses
l
Only in accordance with UL 248
l
System short−circuit current up to 5000 A
rms
: All classes are permissible
l
System short−circuit current up to 50000 A
rms
: Only classes "CC", "J", "T" or
"R" permissible
Cables
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C
Observe all national and regional regulations!
9300
Rated fuse current
Cable cross−section
Fuse
L1, L2, L3, PE
Type
[A]
[AWG]
Operation without mains choke/mains filter
EVS9321−xS
6
18
EVS9322−xS
6
18
EVS9323−xS
10
16
EVS9325−xS
25
10
Operation with mains choke/mains filter
EVS9321−xS
6
18
EVS9322−xS
6
18
EVS9323−xS
10
16
EVS9324−xS
10
16
EVS9325−xS
25
10
EVS9326−xS
25
10
Max. connection cross−section of the terminal strip: AWG 12, with pin−end connector AWG 10
5.4.5
Mains choke/mains filter assignment
9300
Mains choke
Interference voltage category according to EN 61800−3 and motor cable length
Component
Component
Type
C2
max. [m]
C1
max. [m]
EVS9321−xS
EZN3A2400H002
EZN3A2400H002
5
EZN3B2400H002
50
EVS9322−xS
EZN3A1500H003
EZN3A1500H003
5
EZN3B1500H003
50
EVS9323−xS
EZN3A0900H004
EZN3A0900H004
5
EZN3B0900H004
50
EVS9324−xS
EZN3A0500H007
EZN3A0500H007
5
EZN3B0500H007
50
EVS9325−xS
EZN3A0300H013
EZN3A0300H013
5
EZN3B0300H013
50
EVS9326−xS
ELN3−0150H024−001
EZN3A0150H024
5
EZN3B0150H024
50
Installation to UL