Free configuration of analog input signals, Commissioning – Lenze EVS9332xS User Manual
Page 204
Commissioning
Changing the assignment of the control terminals X5 and X6
Free configuration of analog input signals
6.9
6.9.3
l
6.9−3
EDSVS9332S EN 6.0−07/2013
6.9.3
Free configuration of analog input signals
ƒ Internal analog signals can be freely linked with external analog signal
sources:
– Analog inputs X3/1, X3/2 and X3/3, X3/4
ƒ One signal source can be linked with several targets.
The internal analog signals can be linked with an external signal source by
entering the selection figure of the external signal into the configuration
code of the internal analog signal.
Example
ƒ C0780 = 50
ð signal source for the main setpoint (NSET−N) is terminal
X6/1, X6/2
NSET
C0046
NSET-N
DMUX
0
3
0
15
NSET-JOG*1
NSET-JOG *2
NSET-JOG *4
NSET-JOG *8
C0780
C0787/1
C0787/2
C0787/3
C0787/4
C0034
1
2
AIN1
+
+
AIN1-OUT
AIN1-GAIN
AIN1-OFFSET
C0404/1
C0404/2
C0402
C0403
C0400
X6
C0010
+
+
9300vec106
Fig. 6.9−2
Linking analog signal NSET−N with terminal X6/1, X6/2
I
Tip!
ƒ
A list with all selection figures is included in the chapter
"Configuration"
® "Selection lists".
ƒ
For signal linkage we recommend the function block editor in
GDC (ESP−GDC2).
Gain and offset
Set gain (C0027) and offset (C0026) to adapt the input signal to the
application.
Input range of X6/1, X6/2
Input range
C0034
Position of jumper at X3
−10 V ... +10 V
C0034 = 0
6
4
2
5
3
1
+4 mA ... +20 mA
C0034 = 1
6
4
2
5
3
1
−20 mA ... +20 mA
C0034 = 2
)
Note!
Different settings in C0034 and of X3 result in a wrong input
signal.
Description
Linking signals
Adjustment