Configuration, Code table – Lenze EVS9332xS User Manual
Page 246
Configuration
Code table
8.4
l
8.4−5
EDSVS9332S EN 6.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0051 MCTRL−NACT
g −30000
{1 rpm}
30000 Actual speed
C0052 MCTRL−UMOT
g 0
{1 V}
800 Motor voltage
C0053 UG−VOLTAGE
g 0
{1 V}
900 DC−bus voltage
C0054 IMOT
g 0.0
{0.1 A}
300.0 Current motor current I
mot
MCTRLfunction block
l
Read only
l
MCTRL−IACT = 100 % = C0022
C0056 MCTRL−MSET2
g −100.00
{0.01 %}
100.00 MCTRL−MSET2 (Mset)
Torque setpoint (n−controller output)
C0057 MAX TORQUE
g 0
{1 Nm}
500 Maximum torque
Maximum possible torque of the drive
configuration
l
Depending on C0022, C0086
C0058 ROTOR DIFF
−90.0 −180.0
{0.1 °}
179.9 Rotor displacement angle of motor (offset
angle)
Zero phase of the rotor for synchronous
motors (C0095).
If a resolver is selected in C0025 or C0490,
C0058 is set to −90°.
l
Lenze motor with resolver: C0058 = −90°
l
Lenze motor with absolute value encoder:
C0058 = 0°
C0059 MOT POLE NO.
g 1
{1}
50 Number of motor pole pairs
C0060 ROTOR POS
g 0
{1}
2048 Motor rotor position
l
1 revolution = 2048 inc
C0061 HEATSINK
TEMP
g 0
{1 °C}
100 Heatsink temperature
C0063 MOT TEMP
g 0
{1 °C}
200 Motor temperature
C0064 UTILIZATION
g 0
{1 %}
150 Device utilisation I × t of the last 180 s
l
C0064 >100 % releases trip OC5
l
Trip reset is only possible if C0064 < 95 %
C0066 MOTOR LOAD
g 0
{1 %}
250 I
2
× t utilisation of the motor
C0067 ACT TRIP
g All fault
messages
à Selection list 10 Trip error message
Current fault message
C0070 VP SPEED CTRL
à
0.0
{0.5}
255.0 V
pn
speed controller
à
Depending on C0086
l
Change of C0086 resets value to the
assigned Lenze setting
C0071 TN SPEED CTRL
à
1.0
{0.5 ms}
600.0 T
nn
speed controller
At >512 ms the function is deactivated
à
Depending on C0086
l
Change of C0086 resets value to the
assigned Lenze setting
C0072 TD SPEED CTRL
0.0
0.0
{0.1 ms}
32.0 T
dn
speed controller
C0075 VP CURR CTRL
0.35
0.00
{0.01}
15.99 V
pi
current controller
l
Depending on C0086
l
Change of C0086 resets value to the
assigned Lenze setting
C0076 TN CURR CTRL
1.8
0.5
{0.1 ms}
2000.0 T
ni
current controller
At 2000 ms the function is deactivated
l
Depending on C0086
l
Change of C0086 resets value to the
assigned Lenze setting
C0077 VP FIELD CTRL
0.25
0.00
{0.01}
15.99 V
pF
field controller
C0078 TN FIELD CTRL
15.0
1.0
{0.5 ms}
8000.0 T
nF
field controller
At 8000 ms the function is deactivated