Configuration – Lenze EVS9332xS User Manual
Page 256
Configuration
Code table
8.4
l
8.4−15
EDSVS9332S EN 6.0−07/2013
IMPORTANT
Possible settings
Code
Selection
Lenze
Designation
No.
C0356
0
{1 ms}
65000 CAN
System bus time settings
1 CAN BOOT UP
3000
Required for CAN interconnection without
master
2 OUT2 CYCLE
0
0 = event−controlled process data transfer
3 OUT3 CYCLE
0
>0 = cyclic process data transfer
4 CAN DELAY
20
When the "Operational" NMT status is
reached (after "Pre−operational" or
"Stopped"), the ˜CANdelay˜ delay time is
started. After the delay time has elapsed, the
PDO´s CAN−OUT2 and CAN−OUT3 are
transmitted for the first time.
C0357
0
{1 ms}
65000 CAN
System bus monitoring times
l
After a fault message, the CAN objects
remain in receive position
1 CE1 MONIT
TIME
3000
CAN−IN1
2 CE2 MONIT
TIME
3000
CAN−IN2
3 CE3 MONIT
TIME
3000
CAN−IN3
C0358 RESET NODE
0
0
1
No function
CAN reset
CAN
Establish nodal reset pointfor system bus
C0359 CAN STATE
g 0
1
2
3
Operational
Pre−Operational
Warning
Bus off
CAN
System bus status
C0360
g 0
65535 CAN
Telegram counter (number of telegrams)
Count values > 65535: Restart with 0
1 MESSAGE OUT
All telegrams sent
2 MESSAGE IN
All telegrams received
3 MESSAGE
OUT1
Telegrams sent on CAN−OUT1
4 MESSAGE
OUT2
Telegrams sent on CAN−OUT2
5 MESSAGE
OUT3
Telegrams sent on CAN−OUT3
6 MESSAGE
OUT1
Telegrams sent via parameter channel 1
7 MESSAGE
OUT2
Telegrams sent on parameter channel 2
8 MESSAGE IN1
Telegrams received from CAN−IN1
9 MESSAGE IN2
Telegrams received from CAN−IN2
10 MESSAGE IN3
Telegrams received from CAN−IN3
11 MESSAGE IN1
Telegrams received from parameter
channel 1
12 MESSAGE IN2
Telegrams received via parameter channel 2