4. Commissioning
4−19
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
4.5.2
Controlling the CMAX in record select operating mode
I/O data: Record select mode
Data
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
O data
CCON
CPOS
Record no. Reserved
Reserved
I data
SCON
SPOS
Record no. RSB
Primary actual value (actual position, actual
force)
Allocation of the control bytes (overview)
CCON
Byte 1
B7
OPM2
B6
OPM1
B5
LOCK
B4
ć
B3
RESET
B2
BRAKE
B1
STOP
B0
ENABLE
y
To select the operatĆ
ing mode, see
Tab. 4/3
Software
access
blocked
ć
Acknow−
ledge malĆ
function
Release
brake
Stop
Enable
drive
CPOS
Byte 2
B7
ć
B6
CLEAR
B5
TEACH
B4
JOGN
B3
JOGP
B2
HOM
B1
START
B0
HOLD
y
ć
ć
Teach
value
Jog,
negative
Jog, posiĆ
tive
Start
homing
Start
positionĆ
ing job
ć
Record no. Byte 3: Record number of the record to be started.
Allocation of the status bytes (overview)
SCON
Byte 1
B7
OPM2
B6
OPM1
B5
FCT_MMI
B4
24VL
B3
FAULT
B2
WARN
B1
OPEN
B0
ENABLED
Byte 1
For operating mode
acknowledgement,
see Tab. 4/3
Device
control
software
Load voltĆ
age apĆ
plied
MalfuncĆ
tion
Warning
Operation
enabled
Drive
enabled
SPOS
Byte 2
B7
REF
B6
STILL
B5
DEV
B4
MOV
B3
TEACH
B2
MC
B1
ACK
B0
HOLD
Byte 2
Drive refĆ
erenced
ShutĆ
down
warning
Following
error
Axis movĆ
ing
Teach
acknow−
ledgment
Motion
complete
Acknow−
ledge
start
ć
Record no. Byte 3: Acknowledgement of last started record.
RSB
Byte 4
B7
ć
B6
ć
B5
XLIM
B4
VLIM
B3
RCE
B2
COM1
B1
RCC
B0
RC1
Byte 4
ć
ć
Stroke
limit
reached
Speed
limit
reached
Error
switching
to next
record
Control
mode
acknow−
ledgement
All record
switching
executed
1. record
switch
executed
Primary
actual
value
Byte 5 ... 8: Dependent on the parameterisation: Actual position or actual force in the
configured system of units.