Malfunction group 0 ć Configuration error
CPX error group 100 (CPX−MMI: [Configuration error] )
No.
Message
Cause/description
Error handling
Type
1)
01
The target configuration
differs from the actual
configuration
2)
A component on the axis
string is not part of the
target configuration:
Ĉ Displacement encoder
or sensor interface
(type, length).
Ĉ Cylinder (type, length,
diameter).
Ĉ Valve (size).
·
Check component and
replace, if necessary
·
Accept actual conĆ
figuration (download).
Error
level: F2
Reset: N
The displacement enĆ
coder and the valve have
been exchanged and no
longer match the target
configuration or the
serial numbers have
changed.
·
Check the axis conĆ
figuration. Check to
make sure two axis
strings have not been
interchanged.
02
Unknown valve type
Connected valve is not
supported.
·
Exchange the valve or
·
Update firmware.
Error
level: F2
Reset: N
03
Unknown cylinder type
Connected cylinder or
the sensor interface is
not supported.
·
Exchange the cylinder
or sensor interface or
·
Update firmware.
Error
level: F2
Reset: N
04
Unknown type of disĆ
placement encoder or
sensor interface
Connected displacement
encoder or the sensor inĆ
terface is not supported.
·
Exchange the displaceĆ
ment encoder or senĆ
sor interface or
·
Update firmware.
Error
level: F2
Reset: N
1)
For the error level and reset type, see section 5.2.3.
2)
To avoid tubing errors, the movement test is reset. CMAX has the status C03. The movement test
should be executed again afterwards.