5. Diagnostics and error handling
5−11
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 1 ć Execution error
CPX error group 101 (CPX−MMI: [Execution error] )
Continued
No.
Message
Cause/description
Error handling
Type
1)
16
Dynamic Identification
failed
Incorrect mass was
parameterised or transĆ
ferred to parameter 2.
2)
·
Check the mass and
data.
Error
level: F1
Reset: R
Too much mechanical
backlash in the system.
·
Check the system
structure.
Design not stable
enough.
·
Check the system
structure.
Used tubes are too long.
·
Place the valve closer
to the drive.
Compressed air is not
sufficiently stable.
·
Check the pressure
supply.
17
Identification not yet
executed
Static identification was
not executed at start of
record, during direct
mode or homing.
·
Static identification
executed
Error level: W
Reset: F
18
Clamping unit is still actiĆ
vated, operation enable
not possible
Operation enable
was granted
(CCON.STOP = 1),
although the clamping
unit was not yet reĆ
leased.
·
Cancel operation enĆ
able.
·
Release clamping unit.
Error level: W
Reset: F
19
Invalid change of
operating mode
Changing between reĆ
cord select and direct
modes during an active
positioning job
(SPOS.MC=0).
·
Switch only after
completed positionĆ
ing job
(SPOS.MC = 1)
Error
level: F1
Reset: R
Changing between reĆ
cord select and direct
modes and commissionĆ
ing or parametrising opĆ
erating mode while operĆ
ation enable is active
(CCON.STOP=1).
·
Only switch when
status is stopped".
Set CCON.STOP
= 0 and wait for
SCON.OPEN = 0 and
SPOS.MC = 1
1)
For the error level and reset type, see section 5.2.3.
2)
Parameter 2: Byte 4 ... 8 in commissioning operating mode.