5. Diagnostics and error handling
5−26
Festo P.BE−CPX−CMA X−SYS−EN en 0908NH
Malfunction group 7 ć Controller error
CPX error group 107 (CPX−MMI: [Controller error] )
No.
Message
Cause/description
Error handling
Type
1)
72
System software failure
Internal software error
(firmware).
·
If possible, read
out the diagnostic
memory, save the
project and archive it.
·
Switch the controller
on and off and see
whether the error
occurs again.
·
Contact Support.
Error level: FS
Reset: Poff
73
Controller hardware
defective
No communication with
CMAX possible. Error is
only indicated on the disĆ
play.
·
Exchange CMAX.
Error level: FS
Reset: Poff
74
No firmware
No firmware. No comĆ
munication is possible via
the fieldbus.
·
Firmware download
with FCT.
Error level: FS
Reset: Poff
75
User data damaged
Inconsistent user data.
·
Carry out data reset
and put axis back into
operation.
Error level: F2
Reset: N
76
Watchdog error:
Possible data loss
Data reset required
Internal watchdog error.
·
Carry out data reset
and put axis back into
operation.
·
Contact Support.
Error level: F2
Reset: F
1)
For the error level and reset type, see section 5.2.3.